These trend logs can then be managed through the Trend Log Management feature.

coppertree coppercube

Once the network connection has been established between the CopperCube and the network, the CopperCube lists all the trend logs from the device ranges defined in the CopperCube UI. In the CopperCube UI, under Data, the user can select and manage the trend logs that need to be archived. The Trend Log Management feature includes the following: The archived trend logs will then be transmitted from the CopperCube to the secure servers.

coppertree coppercube

Trend Log Management feature helps the user to select the trend logs that need to be archived. The trend logs and objects from all data acquisition device ranges are collected by the CoppeCube. Setting up multiple sites in a single BACnet network produces communication problems in the CopperCube.CopperCube when connected to the BACnet, communicates with the devices (controllers) defined in the the CopperCube Inclusion Range.

  • You can only set up 1 site per BACnet network.
  • If connecting to multiple sites, the device number does not need to be the same for every site but should be what works best for that particular site. This device number must not conflict with any other device numbers in this BACnet network.
  • You need to enter the connection type and device number for the CopperCube on the BACnet network.
  • It is recommended to minimize spaces and extra capitals. When setting up a building in CopperTree Kaizen to receive the data from the CopperCube, this site name needs to be entered as an exact match. The name should be kept as short as possible as this data is stored repeatedly in the database.
  • The site name is a unique name on your CopperCube with a unique range of devices.
  • You need to consider the following information before you add a site: You can add multiple BACnet sites on the same CopperCube but each site has to have a unique connection to a BACnet network. The data can also be moved to a Kaizen or SQL server. The trend log data is saved internally on the CopperCube.

    COPPERTREE COPPERCUBE ARCHIVE

    These trend logs will be set to Not Archived by default.Īutomatic Trend Logs archive settings under the Sites and Devices Ranges tab 6: Define a BACnet Site and Device Ranges However, in most cases, instead of allowing the system to choose all trend logs, you want to select specific trend logs to archive.Įven though the automatic selection is turned off, CopperCube will still continue to discover new trend logs on the site. Turn Off Automatic Selection of All Trend Logs when the Automatic Trend Log Selection box is selected, CopperCube will automatically discover and archive all trend logs it finds on the site. This setup information is used to ensure that data from CopperCube is mapped to the correct building in Kaizen. This site name will also need to be entered into Kaizen so that your Kaizen account presents the correct data. See Sites for information on defining your site(s).

    COPPERTREE COPPERCUBE SOFTWARE

    The site provides a definition for the CopperCube software to be able to connect to the BACnet network and retrieve data. Settings > Sites and Device Ranges: You must have the CopperCube connected by the BACnet port to the building control network to configure the Sites and Devices. If the setup is correct, you should see the status page of the CopperCube graphical user interface (UI).ĬopperCube IP configurations found under IP settings tab of the settings page 5: Add a site Open a web browser and enter 169.254.8.29 into the address bar.Please note that the CopperCubes purchased prior to March 1, 2014, has a different fixed-IP. Plug a Cat5e cable into your computer’s network port and then into and into the CopperCube fixed-IP Service port (labeled LAN 2).When the CopperCube starts up, it will produce a short beep. Check the Power LED and if it is not on, press and hold the power button until the green power light turns on.Part numbers are 194300 (North America) and 194301 (European) If you did not order a power supply and require one, they are available through online ordering. Connect 24VAC/50VA to the 2-pin screw terminal or 12-28VDC/30W through the barrel connector of a power supply to the CopperCube.The following steps can be taken to set up CopperCubes: 1: Physical Set-Up This document describes the steps that need to be done in order to set up your CopperCube so that it can collect data from your BACnet network. Your CopperCube has come from the factory in an unconfigured state.